Heavy-duty, 1800 RPM propane/natural gas generators. Compliant for applications that only operate upon the loss of a normal power source such as utility.
QuietRun 40 kW LP/Natural Gas Generator - This smooth, quiet 1800 RPM LP/Natural Gas set has plenty of power to run your house, business or off-the-grid hunting cabin. This unit includes a 4.3L 4 cylinder engine, electronic governor (0.5% frequency control), electronic ignition control module, cast iron crankcase with reborable liners, cool flow radiator w/ fan guards, steel skid base w/ vibration isolators (for smooth operation), brushless generator end w/ automatic voltage regulation and control panel with turn-key start and hour meter, muffler and sound enclosure for quiet operation.
Model Number
01722
Electrical Specifications
-
Power Single-Phase
---
Automatic Voltage Regulation
Standard
Is this unit suitable for powering sensitive electronic equipment like a laptop computer?
Yes
Maximum Output
31,000 watts
Continous Output
30,000 watts
Load Amperage at 120 volts
---
Maximum Load
258 Amps
Continous Load
250 Amps
Load Amperage at 240 volts
---
Maximum Load
129 Amps
Continous Load
125 Amps
Sound Level
69 dB(A)
Derate 10% for Natural Gas
Model Number
01722
Engine
-
Type
General Motors
Displacement
3.0L
Operating RPM
1800 RPM
Horsepower
50 HP
Cylinder Block
Cast Iron Block w/ Cast Iron Sleeve
Bore & Stroke
4.00" x 3.6"
Air Cleaner
Heavy Duty Replaceable Dry Element
Oil Capacity (w/ Oil Filter)
6.7 qts.
Recommended Engine Oil
SAE 15W-40
Cylinders
4
Exhaust Outlet
2" OD Muffler Outlet
Governor
Electronic Governor
Frequency Control
+/- 0.5%
Coolant Capacity
Approx. 6.5 Qts
Cooling Fan
Pusher Type
Battery Charging Alternator
Standard - 90 Amps
Fuel
LP/Natural Gas
Starting System
Electric
Model Number
01722
Consumption
-
Consumption at 1/2 Load
1.9 gallons/hour
Consumption at 3/4 Load
2.9 gallons/hour
Consumption at full load
3.3 gallons/hour
Model Number
01722
Control Panel
-
Turn-Key Start
Standard
Hour Meter
Standard
Water Temperature Shutdown
Standard
Oil Pressure Shutdown
Standard
Model Number
01722
Installation Data
-
1. LP/Natural Gas Supply
LP Vapor Withdrawal Tank or Natural Gas Main
2. Gas Meter
Capable Fuel Flow: 425,000 BTUs
3. Safety Shut Off Valve
Not Included
4. Fuel Pressure Supply
Nat. Gas: 5-7" Water Column LP Gas: 11-14" Water Column