HEAVY-DUTY DIESEL GENERATORS (NOT TIER 4 FINAL)


Heavy-duty, 1800 RPM diesel generators. Compliant for applications that only operate upon
the loss of a normal power source such as utility.


Our Reduced Price:$
View  
View  
View  
View  
  


Kubota Powered 25 kW Diesel Generator - Whether for a work site, cabin, lodge, or standby emergency power, this Kubota diesel will do the job every day. Day after day. This unit operates at 1800 RPM and runs smooth and quiet with its residential-grade muffler, acoustic dampening air intake system and 4 point vibration mounts.

This unit features a Kubota V3300, 4 cylinder diesel engine, cast iron crankcase with replaceable wet-type cylinder liners, full flow lube oil filteration, brushless generator with AVR, liquid cooling, +/- 1% AC voltage regulation to protect your electronics, oil & water safety shutdowns, high volume air filter, steel skid base, muffler for quiet operation, glow plugs, turn-key start and hour meter.

HEAVY-DUTY DIESEL GENERATORS (NOT TIER 4 FINAL)

Compliant for applications that only operate upon the loss of a normal power source such as utility or mains grid.



Options   Price
Two-Wire Auto Start + $799
45 Gallon Subbase Fuel Tank + $2295
60 Gallon Subbase Fuel Tank + $2375
100 Gallon Subbase Fuel Tank + $2575





 
Generator   
Automatic Voltage Regulation Standard
Is this unit suitable for powering sensitive electronic equipment like a lap top computer? YES - %1 regulation from no load to full load.
Power Single-Phase
Maximum Output 26,500 Watts
Continuous Output 25,000 Watts
Load Amperage at 120 V
Maximum Load 221 amps
Continuous Load 208 amps
Load Amperage at 240 V
Maximum Load 110 amps
Continuous Load 104 amps
Sound Level at Full Load 74 decibels



Engine   
Model Kubota V3300
Type Vertical In-Line
Horsepower 48 HP
Oil Capacity (w/ Oil Filter) Approx. 11.1 qts
RPM 1800
Cylinders 4
Cylinder Block Cast Iron w/ Cast Iron Sleeves
Bore & Stroke 3.86 x 4.33 in.
Cooling Liquid-Cooling, Pushor Fan
Coolant Capacity Approx. 11.4 Qts
Fuel No. 2 Diesel
Electric Fuel Pump 12 V - Standard
Cold Weather Starting Aid Glow Plugs
Starting System Electric



 
Consumption   
Consumption at 1/2 Load 1.2 gallons/hour
Consumption at 3/4 Load 1.6 gallons/hour
Consumption at Full Load 1.9 gallons/hour



 
Control Panel   
Turn-Key Start Standard
Hour Meter Standard
Water Temperature Shutdown Standard
Oil Pressure Shutdown Standard



Installation Data   
Fuel Inlet Hose Size 3/8"
Fuel Return Hose Size 5/16"
Minimum Power Lead Size 1/0 AWG
No. Power Lead Conductors 4
Exhaust Outlet 2" OD Muffler Outlet
Coolant Recommendation Mixture: 1/2 Anti-Freeze & 1/2 Water
Radiator Dimensions
(L x W x H)
22-3/4" x 9-1/2" x 24"
Fuel Inlet & Return Location Left-Side
Exhaust Direction
(Facing Radiator)
Right-Side
Power Output Location
(Facing Radiator)
Back-Side
Service Points
(Facing Radiator)
Oil Fill: Left-Side
Oil Drain: Left-Side
Air Filter: Left-Side
Oil Filter: Left-Side
Fuel Filter: Left-Side
Battery Type 12 VDC - 575 CCA
Engine Oil Type SAE 15W-40



Maintenance Schedule   
Replace Oil Filter 500 hours / 12 months
Replace Fuel Filter 500 hours / 12 months
Replace Air Filter 500 hours / 12 months
Replace Engine Coolant 500 hours / 12 months
Exercise Generator Under Load Twice each month
Change Oil 500 hours / 12 months



Warranty   
Engine Warranty 3 Years
Generator Warranty 1 Year



 
Dimensions   
Length 57"
Width 26-1/2"
Height 40"
Weight 1800 lbs