Kubota Powered 9,875 Watt Diesel Generator - Whether for a work site, cabin, lodge, or standby emergency power, this Kubota diesel will do the job every day. Day after day. This unit operates at 1800 RPM and with its super quiet muffler, acoustic dampening air intake system and 4 point vibration mounts, runs smooth and quiet.

Like all Central Maine Diesel products, this generator is fully customizable. From enclosure to fuel tank to controls to trailer, you choose the option that is right for you! And, as an added benefit, you will always have the flexibility to upgrade options later.

This unit features a Kubota D1305-BG 1800 RPM diesel engine, brushless generator, liquid cooling, muffler, +/- 1% AC voltage regulation to protect your electronics, oil & water safety shutdowns, high volume air filter, steel skid base, glow plugs for cold weather starting and control panel w/ turn-key start and hour meter.


OPEN BOX
PERKINS DIESEL


55 GALLON DRUM
FUEL TANK KIT



Options   Price
55 Gallon Fuel Drum Kit + $195
Sound Proof Enclosure + $3275
60 Gallon Subbase Fuel Tank + $2375
100 Gallon Subbase Fuel Tank + $2575
100 Amp Automatic Transfer Switch + $1599





.
Generator
Maximum Output 9,875 watts
Continous Output 8,750 watts
Power One-Phase MLS4-Y
Load Amperage at 120 volts ---
Maximum Load 82 Amps
Continous Load 72.9 Amps
Load Amperage at 240 volts ---
Maximum Load 41 Amps
Continous Load 36.4 Amps
Sound Level @ 23 ft(7 m) at full load 70 dB(A)



Engine
Model Kubota D1305-E3BG
Type Vertical 4-Cycle
Fuel Injection System Indirect Injection
Oil Capacity (w/ Oil Filter) Approx. 4.5 qts
Horsepower 17.6 HP @ 1800 RPM
RPM 1800
Displacement 1.2 L
Cylinders 3
Bore & Stroke 3.07 in. x 3.46 in.
Cylinder Block Cast Iron w/ Cast Iron Sleeves
Cooling Liquid-Cooling, Pushor Fan
Coolant Capacity Approx. 6 Qts
Fuel No. 2 Diesel
Cold Weather Starting Aid Glow Plugs
Starting System Electric



Engine
Consumption at 1/2 load 0.41 gallons/hour
Consumption at 3/4 load 0.63 gallons/hour
Consumption at full load 0.84 gallons/hour



.
Control Panel
Turn-Key Start Standard
Hour Meter Standard
Water Temperature Shutdown Standard
Oil Pressure Shutdown Standard



Installation Data
Fuel Inlet Hose Size 3/8"
Fuel Return Hose Size 5/16"
Minimum Power Lead Size No. 4 AWG
No. Power Lead Conductors 4
Exhaust Outlet 2" OD Muffler Outlet
Coolant Recommendation Mixture: 1/2 Anti-Freeze & 1/2 Water
Radiator Dimensions
(L x D x H)
22-3/4" x 9-1/2" x 24"
Fuel Inlet & Return Location
(Facing Radiator)
Left-Side
Exhaust Direction
(Facing Radiator)
Right-Side
Power Output Location (Facing Radiator) Back-Side
Service Points
(Facing Radiator)
Oil Fill: Left-Side
Oil Drain:Left-Side
Air Filter: Back-Side
Oil Filter: Left-Side
Fuel Filter: Left-Side
Battery Type 12 VDC - 575 CCA
Engine Oil Type SAE 15W-40



Maintenance Schedule
Replace Oil Filter 500 hours / 12 months
Replace Fuel Filter 500 hours / 12 months
Replace Air Filter 500 Hours / 12 months
Replace Engine Coolant 500 Hours / 12 months
Exercise Generator Under Load Twice each month
Change Oil 500 hours / 12 months



Warranty
Engine Warranty 3 Years
Generator Warranty 1 Year
100% Coverage for Parts & Labor Standard



.
Dimensions
Length 38"
Width 19-1/2"
Height 27"
Dry weight 645 lbs



   PRINTABLE VERSION


 